Melsec-q, 8 opr control, Restrictions – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 287: Precautions during operation

Advertising
background image

8 - 9

MELSEC-Q

8 OPR CONTROL

Restrictions

(1) Always limit the servomotor torque after the "

Pr.47

Creep speed" is reached. If the

torque is not limited, the servomotor may fail when the machine presses against the
stopper. (Refer to Section 12.4.2 "Torque limit function".)

(2) In the "stopper method 1)", the OPR retry function is unusable.

Precautions during operation

(1) Set a value in the "

Pr.49

OPR dwell time" that is equal to or higher than the

movement time from the near-point dog ON to the time the machine presses against
the stopper.

(2) The workpiece will continue decelerating and stop if the "

Pr.49

OPR dwell time"

elapses during deceleration from the "

Pr.46

OPR speed", thus causing an error

"Dwell time fault (error code: 205)".

Md.34 Movement amount
after near-point dog ON

Md.26 Axis operation status

t

V

ON

OFF

ON

OFF

OFF

0

In error

Address at stop

" Pr.49 OPR
dwell time" setting

Pr. 46 OPR speed

Pr. 47 Creep speed

Machine OPR start
(Positioning start signal)

OPR request flag
[ Md.31 Status : b3]

OPR complete flag
[ Md.31 Status : b4]

Md.20 Current feed value

Md.21 Machine feed value

Standing by

Inconsistent

Inconsistent

In OPR

Value the machine moved is stored

Stops at stopper

Fig. 8.5 Operation when the dwell time elapses during deceleration from the OPR speed

Advertising