3 list of input/output signal details, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 68

Advertising
background image

3 - 20

MELSEC-Q

3 SPECIFICATIONS AND FUNCTIONS

3.4.3 List of input/output signal details

The details of each QD75 external device connection connector are shown below:

Pin No.

Signal name

AX1

AX2

AX3

AX4

Signal details

(Negative logic is selected by external I/O signal logic selection)

Manual pulse generator A

phase

Manual pulse generator B

phase

1A19

1A20

• Input the pulse signal from the manual pulse generator A phase and B

phase.

• If the A phase leads the B phase, the positioning address will increase at the

rising and falling edges of each phase.

• If the B phase leads the A phase, the positioning address will decrease at the

rising and falling edges of each phase.

[When increased]

[When decreased]

Manual pulse generator A

common

Manual pulse generator B

common

1B19

1B20

+1+1+1+1+1+1+1+1

-1 -1 -1 -1 -1 -1 -1 -1

A phase

B phase

Positioning
address

A phase

B phase

Positioning
address

Zero signal (+24V)

1A8

1B8

2A8

2B8

Zero signal (+5V)

1A9

1B9

2A9

2B9

• Input the zero signal for machine OPR.

Use the pulse encoder's zero signal and so on.

• Also use this signal when the machine OPR method is the stopper method

and the OPR complete is input from an external source.

• The zero signal is detected at turning from OFF to ON.

Zero signal common

1A10 1B10 2A10 2B10 • Common for zero signal (+5V) and zero signal (+24V).

Pulse output F (+) <CW+>

Pulse output F (–) <CW–>

1A15

1A16

1B15

1B16

2A15

2A16

2B15

2B16

Pulse output R (+) <CCW+>

Pulse output R (–)

<CCW–>

1A17

1A18

1B17

1B18

2A17

2A18

2B17

2B18

• Output the positioning pulses and pulse sign for the differential driver output

system compatible drive unit.

(QD75D

only)

Pulse output F

<CW>

Pulse output F common

<CWCOM>

1A15

1A16

1B15

1B16

2A15

2A16

2B15

2B16

Pulse output R

<CCW>

Pulse output R common

<CCWCOM>

1A17

1A18

1B17

1B18

2A17

2A18

2B17

2B18

• Output the positioning pulses and pulse sign for the open collector output

system compatible drive unit.

(QD75P

only)

Upper limit signal

1A1

1B1

2A1

2B1

• This signal is input from the limit switch installed at the upper limit position of

the stroke.

• Positioning will stop when this signal turns OFF.

• When OPR retry function is valid, this will be the upper limit for finding the

near-point dog signal.

Lower limit signal

1A2

1B2

2A2

2B2

• This signal is input from the limit switch installed at the lower limit position of

the stroke.

• Positioning will stop when this signal turns OFF.

• When OPR retry function is valid, this will be the lower limit for finding the

near-point dog signal.

Near-point dog signal

1A3

1B3

2A3

2B3

• This signal is used for detecting the near-point dog during OPR.

• The near-point dog signal is detected at turning from OFF to ON.