Melsec-q, Remark, Appendix - 39 – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 681: Input signal logic selection" and, And servo amplifier. the qd75d, Is initially set to negative logic

Advertising
background image

Appendix - 39

MELSEC-Q

APPENDICES

Appendix 4.3 Connection example of QD75D and MR-C A (Differential driver)

5

PULSE F+

15

PULSE F-

16

PULSE R+

17

PULSE R-

18

CLEAR

13

CLEAR COM

14

PG024

8

PG0 COM

10

DOG

3

FLS

1

RLS

2

STOP

4

COM

7

A19
B19
A20
B20

PULSER A+

QD75D

PP
PG
NP
NG
CR
SG
V+
OP
SD

LSP
LSN

9

10

7
8

13
12

1
4

11

15
14

Near-point dog

Upper limit
Lower limit
Stop
External command

5V

A
B

0V

+5V

Manual pulse generator
MR-HDP01

5G

Servo ON

3

2

3

1

CN1

Power supply

Single-phase 200VAC (A type) or

single-phase 100VAC (A1 type)

NF

MC

L1

L2

U
V

W

U
V

W

E

SM

EMG

24VDC

Cutoff by servo ON signal
OFF alarm signal.

HC-PQ
series motor

Detector

CN2

TE1

READY

CHG
COM

PULSER A-
PULSER B+
PULSER B-

11

5
6

SON

ALM
V24

2

20

17

C

P

Regenerative resistor is an external option.

Servo READY

2

RA1

Fault

24V power
supply

+

-

24V, 0.2 A or higher

Configure a sequence to turn OFF the
MC at alarms and emergency stops.

MR-C A or MR-C A1

Within 10m 4

Forward run stroke end

Reverse run stroke end

Electromagnetic
brake

15
16

PULSE F
PULSE COM
PULSE R
PULSE COM

17
18

QD75P

When connecting an open collector,
make connection as shown below.

9

12

PP
SG
NP

7

CN1

RDY COM

12

REMARK

(1) It is recommended to make differential driver connection since differential driver connection is more excellent than

open collector connection in max. output pulse and max. connection distance between servos. (Refer to Section
3.1 "Performance specifications".)

(2) 1: The logic for each I/O terminal can be changed with "

Pr.22

Input signal logic selection" and "

Pr.23

Output

signal logic selection" in detailed parameters 1. (Negative logic is used for all terminals in the example above.)

(3) 2: The QD75D

upper limit (FLS) and lower limit (RLS) are used in the OPR retry function. Set these signals

inside the servo amplifier limit switches.

(4) 3: These are limit switches for the servo amplifier (for stop).
(5) 4: This indicates the distance between the QD75D

and servo amplifier.

(6) 5: Use the same logic (positive logic/negative logic) for the QD75D

and servo amplifier. The QD75D

is

initially set to negative logic.

Advertising