12 - 25

MELSEC-Q

12 CONTROL SUB FUNCTIONS

[4] Setting the torque limit function

(1) To use the "torque limit function", set the "torque limit value" in the

parameters shown in the following table, and write them to the QD75.
The set details are validated at the rising edge (OFF ON) of the PLC
READY signal (Y0).

Setting item

Setting

value

Setting details

Factory-set
initial value

Pr.17

Torque limit
setting value

Set the torque limit value as a percentage.

300

Pr.54

OPR torque limit
value

Set the torque limit value after the " Pr.47 Creep

speed" is reached. Set as a percentage.

300

Refer to Section 5.2 "List of parameters" for setting details.

(2) The "torque limit value" set in the QD75 is set in the "

Md.35

Torque limit

stored value". The "

Md.35

Torque limit stored value" in the sequence

program is transferred to the "D/A converter module", and the torque is
limited.

PLC CPU

Buffer memory

Drive unit

Writing by a
TO command

Stored torque
limit value

826

D/A convertor module

Reading by a

FROM command

QD75

Torque limiting

Positioning control

Fig. 12.14 Limiting the torque to the drive unit (Axis 1)

The following table shows the "

Md.35

Torque limit stored value" of the

buffer memory address.

Buffer memory address

Monitor item

Monitor

value

Storage details

Axis

1

Axis

2

Axis

3

Axis

4

Md.35

Torque limit stored
value

The "torque limit value" valid at that time is

stored. (

Pr.17

,

Pr.54

, or

Cd.22

)

826

926 1026 1126

Refer to Section 5.6 "List of monitor data" for information on the setting details.

REMARK

Parameters are set for each axis.

It is recommended that the parameters be set whenever possible with GX

Configurator-QP. Execution by sequence program uses many sequence programs

and devices. The execution becomes complicated, and the scan times will

increase.