MELSEC-Q

6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL

6.5.6 Stop program

The axis stop signal [Y4, Y5, Y6, Y7] or a stop signal from an external source is used

to stop the control.

Create a program to turn ON the axis stop signal [Y4, Y5, Y6, Y7] as the stop program.

The process for stopping control is explained below.

Each control is stopped in the following cases.

(1) When each control is completed normally.

(2) When the drive unit READY signal is turned OFF.

(3) When a PLC CPU error occurs

(4) When the PLC READY signal is turned OFF.

(5) When an error occurs in QD75.

(6) When control is intentionally stopped

(Stop signal from PLC CPU turned ON, stop signal from peripheral devices)

The stop process for the above cases is shown below.

(Excluding item (1) above "When each control is completed normally".)

[1] Stop

process

Stop process

OPR control

Manual control

Stop cause

Stop

axis

M code

ON

signal

after stop

Axis

operation

status

(

Md.26

)

after

stopping

Machine

OPR

control

Fast OPR

control

Major

positioning

control

High-level

positioning

control

JOG/

Inching

operation

Manual

pulse

generator

operation

Forced stop

Drive unit
READY signal
OFF

Each

axis

No

change

During
error

Immediate stop

Deceleration
stop

Fatal stop
(Stop group 1)

Hardware stroke
limit upper/lower
limit error
occurrence

Each

axis

No

change

During
error

Deceleration stop/sudden stop

(Select with "

Pr.37

Sudden stop group 1 sudden stop

selection".

Deceleration
stop

PLC CPU error
occurrence

No

change

PLC READY
signal OFF

Turns

OFF

Emergency stop
(Stop group 2)

Error in test
mode

All axes

No

change

During
error

Delegation stop/sudden stop

(Select with "

Pr.38

Sudden stop group 2 sudden stop

selection".

Deceleration
stop

Axis error
detection (Error
other than stop
group 1 or 2)

Relatively safe
stop
(Stop group 3)

"Stop" input from
peripheral device

Each

axis

No

change

During
error

"Stop signal" ON
from external
source

Intentional stop
(Stop group 3)

"Axis stop signal"
ON from PLC
CPU

Each

axis

No

change

During
stop
(during
standing
by)

Deceleration stop/sudden stop

(Select with "

Pr.39

Sudden stop group 3 sudden stop

selection".

Deceleration
stop