15 - 34

MELSEC-Q

15 TROUBLESHOOTING

Classification

of warnings

Warning

code

Warning name

Warning

Operation status at warning

occurrence

Manual pulse

generator

401

Outside manual
pulse generator
input magnification
range

The manual pulse generator 1 pulse
input magnification is set at 0 or 101
or higher.

• When input magnification is set at

101 or higher: Re-set to 100.

• When input magnification is set at 0:

Re-set to 1.

500

Deceleration/stop
speed change

The speed change request is issued
during deceleration stop.

The speed change is not carried out.

501

Speed limit value
over

The new value exceeds the speed
limit value when the speed is
changed during operation.

• The speed is controlled with the

speed limit value.

• The "speed limiting flag" is turned

ON.

503

M code ON signal
ON start

The M code ON signal is turned ON
when the positioning data is
executed.

Continue executing the positioning
data.

505

No operation
termination setting

In the positioning by block starting,
the 50th point of the positioning start
data is set to CONTINUE.

The operation is terminated.

506

FOR to NEXT nest
construction

FOR to NEXT is nested.

508

Speed-position
switching (during
acceleration) signal
ON

The switching signal for speed-
position switching control (INC
mode) is turned ON during
acceleration.

The operation is continued.

509

Insufficient
remaining distance

• At a continuous operation interrupt

request, the distance required
deceleration stop is not long
enough.

• At a speed change request, the

remaining distance is shorter than
the distance required for speed
change.

• When a command speed is

changed:
Change to a value as near a new
speed value as possible.

• When a target position is changed:

Adjust the speed to a value as
near the command speed as
possible, and then change to a
target position.

(When the operation pattern is a
continuous path control, ignore the
operations stated above.)

511

Step not possible

Code 1 is set for the step start
information when the step is outside
standby.

The step will not start.

512

Illegal external
command function

The detailed parameter 2 "External
command function selection" setting
range is exceeded.

Even if the external command signal
is turned ON, the system will not
perform anything.

Positioning

operation

513

Insufficient
movement amount

The movement amount is not large
enough for automatic deceleration.

The system stops immediately after it
reaches the positioning address.