Melsec-q, 12 control sub functions, Point – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 544: 3] precautions during control

Advertising
background image

12 - 68

MELSEC-Q

12 CONTROL SUB FUNCTIONS

Da. 1 Operation pattern

Md. 25 Valid M code

Cd. 7 M code OFF request

11

00

11

Warning occurs at this timing.

t

m1

m3

m2

V

1

OFF

ON

OFF

OFF

ON

ON

0

1 0

0

Positioning start signal

BUSY signal

M code ON signal

Positioning

m1 and m3 indicate set M codes.

[XC, XD, XE, XF]

[Y10, Y11, Y12, Y13]

[X4, X5, X6, X7]

Fig. 12.40 Warning due to an M code ON signal during continuous path control

POINT

If the M code output function is not required, set a "0" in setting item "

Da.10

M

code" of the positioning data.

[3] Precautions during control

(1) During interpolation control, the reference axis M code ON signal is turned

ON.

(2) The M code ON signal will not turn ON if "0" is set in "

Da.10

M code". (The

M code will not be output, and the previously output value will be held in

"

Md.25

Valid M code".)

(3) If the M code ON signal is ON at the positioning start, an error "M code ON

signal start (error code: 536)" will occur, and the positioning will not start.

(4) If the PLC READY signal (Y0) is turned OFF, the M code ON signal will turn

OFF and "0" will be stored in "

Md.25

Valid M code".

(5) If the positioning operation time is short during continuous path control, there

will not be enough time to turn OFF the M code ON signal, and a warning "M
code ON signal ON (error code: 503)" may occur. In this case, set a "0" in

the "

Da.10

M code" of that section's positioning data.

(6) In the AFTER mode during speed control, the M code is not output and the

M code ON signal does not turn ON.

(7) If current value changing where "9003" has been set to " Cd.3 Positioning

start No." is performed, the M code output function is made invalid.

Advertising