12 1-axis speed control, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 367

Advertising
background image

9 - 67

MELSEC-Q

9 MAJOR POSITIONING CONTROL

9.2.12 1-axis speed control

In "1-axis speed control" (" Da.2 Control system" = Forward run: speed 1, Reverse

run: speed 1), control is carried out in the axis direction in which the positioning data

has been set by continuously outputting pulses for the speed set in " Da.8 Command

speed" until the input of a stop command.

The two types of 1-axis speed control are "Forward run: speed 1" in which the control

starts in the forward run direction, and "Reverse run: speed 1" in which control starts in

the reverse run direction.

Operation chart

The following chart shows the operation timing for 1-axis speed control with axis 1
as the reference axis.

The "in speed control" flag (

Md.31

Status: b0) is turned ON during speed control.

The "Positioning complete signal" is not turned ON.

t

V

BUSY signal

OFF

ON

Positioning start signal

OFF

ON

Positioning complete signal

OFF

Axis stop signal
(stop command) [Y4]

OFF

ON

Does not turn ON even
when control is stopped
by stop command.

OFF

ON

Md.31 Status:b0

In speed control flag

Da. 8 Command speed

[Y10]

[XC]

[X14]

Fig.9.9 1-axis speed control operation timing