1 data required for high-level positioning control, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 417

Advertising
background image

10 - 3

MELSEC-Q

10 HIGH-LEVEL POSITIONING CONTROL

10.1.1 Data required for high-level positioning control

"High-level positioning control" is executed by setting the required items in the "block

start data" and "condition data", then starting that "block start data". Judgment about

whether execution is possible, etc., is carried out at execution using the "condition

data" designated in the "block start data".

"Block start data" can be set for each No. from 7000 to 7004 (called "block Nos."), and

up to 50 points can be set for each axis. (This data is controlled with Nos. called

"points" to distinguish it from the positioning data. For example, the 1st block start data

item is called the "1st point block start data" or "point No. 1 block start data".)

"Condition data" can be set for each No. from 7000 to 7004 (called "block Nos."), and

up to 10 data items can be set for each axis.

The " block start data" and "condition data" are set as 1 set for each block No.

The following table shows an outline of the " block start data" and "condition data"

stored in the QD75.

Setting item

Setting details

Da.11

Shape

Set whether to end the control after executing only the "block
start data" of the shape itself, or continue executing the "block
start data" set in the next point.

Da.12

Start data No.

Set the "positioning data No." to be executed.

Da.13

Special start
instruction

Set the method by which the positioning data set in Da.12

will be started.

Block start data

Da.14

Parameter

Set the conditions by which the start will be executed

according to the commands set in Da.13 . (Designate the

"condition data No." and "No. of repetitions".)

Setting item

Setting details

Da.15

Condition target

Designate the "device", "buffer memory storage details", and
"positioning data No." elements for which the conditions are
set.

Da.16

Condition
operator

Set the judgment method carried out for the target set in

Da.15 .

Da.17

Address

Set the buffer memory address in which condition judgment is

carried out (only when the details set in Da.15 are "buffer

memory storage details").

Da.18

Parameter 1

Set the required conditions according to the details set in

Da.15 and Da.16 .

C

ondition data

Da.19

Parameter 2

Set the required conditions according to the details set in

Da.15 and Da.16 .