MELSEC-Q

6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL

REMARK

Restarting after stopping is possible even for the following control.

Incremental system position control

Continuous positioning control

Continuous path control

Block start

[3] Control data requiring setting

Set the following data to execute restart.

Buffer memory address

Setting item

Setting

value

Setting details

Axis 1 Axis 2 Axis 3 Axis 4

Cd.6

Restart command

1

Set "1: Restarts".

1503

1603

1703

1803

Refer to Section 5.7 "List of control data" for details on the setting details.

[4] Starting conditions

The following conditions must be satisfied when restarting. (Assemble the

required conditions into the sequence program as an interlock.)

(1) Operation state

"

Md.26

Axis operation status" is "1: Stopped"

(2) Signal state

Device

Signal name

Signal state

Axis 1 Axis 2 Axis 3 Axis 4

PLC READY signal

ON PLC CPU preparation completed

Y0

QD75 READY signal

ON QD75 preparation completed

X0

Synchronization flag

ON

QD75 buffer memory
Accessible

X1

Axis stop signal

OFF Axis stop signal is OFF

Y4

Y5

Y6

Y7

M code ON signal

OFF M code ON signal is OFF

X4

X5

X6

X7

Error detection signal

OFF No error is present

X8

X9

XA

XB

BUSY signal

OFF BUSY signal is OFF

XC

XD

XE

XF

Interface
signal

Start complete signal

OFF Start complete signal is OFF

X10

X11

X12

X13

Drive unit READY signal

ON Drive unit preparation completed

Stop signal

OFF Stop signal is OFF

Upper limit (FLS)

ON Within limit range

External
signal

Lower limit (RLS)

ON Within limit range

: When the synchronous setting of the PLC CPU is made in the nonsynchronous mode, this must be

provided as an interlock.
When it is made in the synchronous mode, no interlock must be provided in the program because the
flag is turned ON when calculation is run on the PLC CPU.