Melsec-q, 14 dedicated instructions, Errors – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 592: Precautions

Advertising
background image

14 - 10

MELSEC-Q

14 DEDICATED INSTRUCTIONS

END

processing

END

processing

END

processing

END

processing

OFF

OFF

OFF

ON

ON

ON

When

completed

abnormally

When

completed normally

1 scan

PSTRT instruction
execution completion

Sequence program

PSTRT instruction

Complete device

Complete state display
device

[Errors]

(1) When an PSTRT instruction is completed abnormally, the error complete signal

((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1).

Check and take a measure against the error referring to Section 15.2 "List of error

codes".

[Precautions]

(1) When positioning is started by the PSTRT instruction, the positioning start

signals (Y10 to Y13) and start complete signals (X10 to X13) will not turn ON.

To confirm that positioning control is being executed, use the PSTRT start

command or BUSY signals (XC to XF).

(2) If, after positioning has been started by the PSTRT instruction, a stop command

is input before positioning is complete, the complete device (D) turns ON one scan

and the execution of the PSTRT instruction is completed.

(3) The following dedicated instructions cannot be executed simultaneously for the

same axis.

(Can be executed simultaneously for different axes.)

• Positioning start instructions (PSTRT1 to PSTRT4)

• Absolute position restoration instructions (ABRST1 to ABRST4)

• Teaching instructions (TEACH1 to TEACH4)

(4) The PSTRT instruction can only be executed when the QD75 READY signal

(X0) is turned ON.

Even if the PSTRT instruction execution request is given when the QD75

READY signal is turned OFF, the PSTRT instruction will not be executed. (not

processed.)

Before executing the PSTRT instruction, turn ON the PLC READY signal (Y0),

and turn ON the QD75 READY signal (X0).

(5) When the remote I/O station (Q Corresponding MELSECNET/H network remote

I/O module) is used, the dedicated instruction (PSTRT ) is unusable.

: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H

Network System Reference Manual (Remote I/O Network).