2 operation patterns of major positioning controls, Melsec-q, Point – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 305

Advertising
background image

9 - 5

MELSEC-Q

9 MAJOR POSITIONING CONTROL

9.1.2 Operation patterns of major positioning controls

In "major positioning control" (high-level positioning control), " Da.1 Operation
pattern" can be set to designate whether to continue executing positioning data after
the started positioning data. The "operation pattern" includes the following 3 types.

Positioning complete

(1) Independent positioning control
(operation pattern: 00)

Positioning continue

(2) Continuous positioning control
(operation pattern: 01)

(3) Continuous path control
(operation pattern: 11)

The following shows examples of operation patterns when "1-axis linear control (ABS
linear 1)" is set in positioning data No. 1 to No. 6 of axis 1. Details of each operation
pattern are shown on the following pages.

< Operation example when "1-axis linear positioning" is set in the positioning data of axis 1 >

(Direction in which axis 1 addresses increase)

1-axis linear control

(One motor is driven, and positioning is carried out to an addresses designated in one direction.)

Speed

Positioning data No.1

0

Operation pattern = 11: Continuous path control

Positioning to address [A] at command speed [a]

No.2

No.3

No.4

No.5

Address

a

b

NO.1

No.2

No.3

No.4

No.5

Speed is changed
without stopping

The machine stops, and
then continues the next
positioning.

Positioning is terminated

No.6

Control stop

No.1 Start

11

11

01

01

00

Time

Da. 1 Operation pattern

(Positioning data)

(Setting details)

Positioning to address [C] at command speed [a]

Positioning to address [D] at command speed [b]

Positioning to address [E] at command speed [a]

Positioning to address [F] at command speed [a]

Positioning to address [B] at command speed [b]

Operation pattern = 11: Continuous path control

Operation pattern = 01:

Continuous positioning control

Operation pattern = 00: Independent positioning control
(Positioning complete)

Operation pattern = 11: Continuous path control

Operation pattern = 01:

Continuous positioning control

A

E

D

C

B

F

For

POINT

The BUSY signal [XC, XD, XE, XF] turns ON even when position control of
movement amount 0 is executed. However, since the ON time is short, the ON
status may not be detected in the sequence program.