9 - 16

MELSEC-Q

9 MAJOR POSITIONING CONTROL

9.1.4 Confirming the current value

Values showing the current value

The following two types of addresses are used as values to show the position in
the QD75.
These addresses ("current feed value" and "machine feed value") are stored in the
monitor data area, and used in monitoring the current value display, etc.

Current feed value

This is the value stored in " Md.20 Current feed value".

This value has an address established with a "machine OPR" as a
reference, but the address can be changed by changing the current
value to a new value.

This value is updated every 1.8ms.

Machine feed value

This is the value stored in " Md.21 Machine feed value".

This value always has an address established with a "machine OPR"
as a reference. The address cannot be changed, even if the current
value is changed to a new value.

This value is updated every 56.8ms.

The "current feed value" and "machine feed value" are used in monitoring the
current value display, etc.

0

1 to

Md. 20 Current feed value

t

V

OP

20000

Current value changed to

20000 with current value

changing instruction

0

1 to

Md. 21 Machine feed value

Address after the current
value is changed is stored

10000

10000

Address does not change even

after the current value is changed

Fig. 9.8 Current feed value and machine feed value