10 - 8

MELSEC-Q

10 HIGH-LEVEL POSITIONING CONTROL

10.3.2 Block start (normal start)

In a "block start (normal start)", the positioning data groups of a block are continuously

executed in a set sequence starting from the positioning data set in "

Da.12

Start data

No." by one start.

Section [2] shows a control example where the " block start data" and "positioning

data" are set as shown in section [1].

[1] Setting examples

(1) Block start data setting example

Axis 1 block

start data

Da.11

Shape

Da.12

Start data No.

Da.13

Special start

instruction

Da.14

Parameter

1st point

1: Continue

1

0: Block start

2nd point

1: Continue

2

0: Block start

3rd point

1: Continue

5

0: Block start

4th point

1: Continue

10

0: Block start

5th point

0: End

15

0: Block start


(2) Positioning data setting example

Axis 1 position-

ing data No.

Da.1

Operation pattern

1

00: Positioning complete

2

11: Continuous path control

3

01: Continuous positioning control

4

00: Positioning complete

5

11: Continuous path control

6

00: Positioning complete

1 block

1 block

10

00: Positioning complete

15

00: Positioning complete

REMARK

Block :

"1 block" is defined as all the data continuing from the positioning data in which
"continuous positioning control" or "continuous path control" is set in the operation

pattern ( Da.1 ) to the positioning data in which "independent positioning control

(Positioning complete)" is set.