background image

10 - 16

MELSEC-Q

10 HIGH-LEVEL POSITIONING CONTROL

10.4 Setting the condition data

10.4.1 Relation between various controls and the condition data

"Condition data" is set in the following cases.

(1)

When setting conditions during execution of Section 9.2.21 "JUMP instruction"

(major positioning control)

(2)

When setting conditions during execution of "high-level positioning control"

The "condition data" to be set includes the 5 setting items from

Da.15

to

Da.19

, but

the setting requirements and details differ according to the control system and setting

conditions.

The following shows the "condition data" "

Da.15

Condition target" corresponding to

the different types of control.

(The "condition data" settings in this chapter are assumed to be carried out using GX

Configurator-QP.)

High-level positioning control

Major positioning

control

Control type

Da.15

Setting item

Block

start

Wait

start

Simultaneous

start

Repeated start

(For condition)

JUMP instruction

01: Device X

02: Device Y

03: Buffer memory

(1 word)

04: Buffer memory

(2 words)

05: Positioning data

No.

: One of the setting items must be set.
: Setting not possible

REMARK

It is recommended that the "condition data" be set whenever possible with GX

Configurator-QP. Execution by sequence program uses many sequence programs

and devices. The execution becomes complicated, and the scan times will increase.