5 jog operation example, Melsec-q, Point – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 453

Advertising
background image

11 - 13

MELSEC-Q

11 MANUAL CONTROL

11.2.5 JOG operation example

When the "stop signal" is turned ON during JOG operation

When the "stop signal" is turned ON during JOG operation, the JOG operation will
stop by the "deceleration stop" method.
JOG start signals will be ignored while the stop signal is ON.
The operation can be started by turning the stop signal OFF, and turning the JOG
start signal from OFF to ON again.

OFF

ON

BUSY signal[XC, XD, XE, XF] OFF

ON

A JOG start signal OFF ON
while the stop signal is ON will be ignored.

Axis stop signal
[Y4, Y5, Y6, Y7]

OFF

ON

OFF

ON

Forward run JOG start signal
[Y8, YA, YC, YE]

QD75 READY signal [X0]

PLC READY signal [Y0]

OFF

ON

Fig. 11.7 Operation when the stop signal is turned ON during JOG operation

POINT

The QD75 will not receive a "JOG start signal" while the "stop signal" is ON.

Advertising