11 MANUAL CONTROL

11.4.4 Creating a program to enable/disable the manual pulse generator operation

A sequence program must be created to execute a manual pulse generator operation.

Consider the "required control data setting", "start conditions" and "start time chart"

when creating the program.

The following shows an example when a manual pulse generator operation is started

for axis 1.

Required control data setting

The control data shown below must be set to execute a manual pulse generator
operation. The setting is carried out with the sequence program.

Buffer memory address

Setting item

Setting

value

Setting details

Axis

1

Axis

2

Axis

3

Axis

4

Cd.20

Manual pulse
generator 1 pulse
input magnification

1

Set the manual pulse generator 1 pulse input
magnification.

1522

1523

1622

1623

1722

1723

1822

1823

Cd.21

Manual pulse
generator enable
flag

1 (0)

Set "1: Enable manual pulse generator
operation". (Set "0: Disable manual pulse
generator operation" when finished with the
manual pulse generator operation.)

1524 1624 1724 1824

Refer to Section 5.7 "List of control data" for details on the setting details.

Start conditions

The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.

Device

Signal name

Signal state

Axis

1

Axis

2

Axis

3

Axis

4

PLC READY signal

ON PLC CPU preparation completed

Y0

QD75 READY signal

ON QD75 preparation completed

X0

Synchronization flag

ON

QD75 buffer memory

The access is possible.

X1

Axis stop signal

OFF Axis stop signal is OFF

Y4

Y5

Y6

Y7

Start complete signal

OFF Start complete signal is OFF

X10 X11 X12 X13

BUSY signal

OFF QD75 is not operating

XC

XD

XE

XF

Error detection signal

OFF There is no error

X8

X9

XA

XB

Interface
signal

M code ON signal

OFF M code ON signal is OFF

X4

X5

X6

X7

Drive unit READY signal

ON Drive unit preparation completed

Stop signal

OFF Stop signal is OFF

Upper limit (FLS)

ON Within limit range

External
signal

Lower limit (RLS)

ON Within limit range

If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be

inserted in the program for interlocking. If it is set to the synchronous mode, it must not be

inserted in the program for interlocking because it is turned ON when the PLC CPU executes

calculation.