4 external i/o signal logic switching function, Melsec-q, 1] parameter setting details – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 581: 2] precautions on parameter setting

Advertising
background image

13 - 7

MELSEC-Q

13 COMMON FUNCTIONS

13.4 External I/O signal logic switching function

This function switches the signal logic according to the external equipment connected
to the QD75.
For the system in which drive unit READY with b-contact, upper limit switch, and lower
limit switch are not used, the parameter logic setting can be controlled without wiring if
it is changed to a "positive logic".
When the drive unit READY, upper limit switch, and lower limit switch are used, ensure
to use them with b-contact.

The details shown below explain about the "External I/O signal logic switching
function".
[1] Parameter setting details
[2] Precautions on parameter setting

[1] Parameter setting details

To use the "External I/O signal logic switching function", set the parameters
shown in the following table.

Buffer memory address

Setting item

Setting details

Factory-set

initial value

Axis 1 Axis 2 Axis 3 Axis 4

• Selection of logic of signals input from external source to

QD75

b0

Lower limit

b1

Upper limit

b2

Drive unit

READY

b3

Stop signal

b4

External

command signal

b5

Zero signal

b6

Near-point signal

0: Negative logic,

1: Positive logic

b7

Unused

Set "0".

b8

Manual pulse

generator input

0: Negative logic,

1: Positive logic

Pr.22

Input signal logic

selection

b9 to b15

Unused

Set "0".

0

31

181

331

481

• Selection of logic of signals output from QD75 to external

source

b0

Command pulse

signal

0: Negative logic,

1: Positive logic

b1 to b3

Unused

Set "0".

b4

Deviation counter

clear signal

0: Negative logic,

1: Positive logic

Pr.23

Output signal logic

selection

b5 to b15

Unused

Set "0".

0

32

182

332

482

Refer to Section 5.2 "List of parameters" for the information on detail settings.

[2] Precautions on parameter setting

(1) The external I/O signal logic switching parameters are validated when the

PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after
power-on.)

(2) If each signal logic is set erroneously, the operation may not be carried out

correctly.
Before setting, check the specifications of the equipment to be used.

Advertising