The precautions for wiring the QD75 are given below. Refer to this section as well as

"4.1.3 Handling precautions" when carrying out the work.

4.3.1 Precautions for wiring

(1) Always confirm the terminal layout before connecting the wires to the QD75.

(For the terminal layout, refer to Section 3.4.2 "Signal layout for external device

connection connector".)

(2) Correctly solder the external wiring connector. An incomplete soldering could lead

to malfunctioning.

(3) Make sure that foreign matter such as cutting chips and wire scraps does not

enter the QD75. Failure to observe this could lead to fires, faults or

malfunctioning.

(4) A protective label is attached on the top of the QD75 to avoid foreign matter such

as wire scraps from entering inside during wiring process. Do not remove the label

until the wiring is completed. Before starting the system, however, be sure to

remove the label to ensure heat radiation.

(5) Securely mount the external device connector to the connector on the QD75 with

two screws.

(6) Do not disconnect the external wiring cable connected to the QD75 and the drive

unit by pulling the cable section. When the cable has a connector, be sure to hold

the connector connected to the QD75 and the drive unit. Pulling the cable while it

is connected to the QD75 and the drive unit may lead to malfunctioning or

damage of the QD75 and the drive unit or cable.

(7) Do not bundle or adjacently lay the connection cable connected to the QD75

external I/O signals or drive unit with the main circuit line, power line, or the load

line other than that for the PLC. Separate these by 100mm as a guide. Failure to

observe this could lead to malfunctioning caused by noise, surge, or induction.

(8) The shielded cable for connecting QD75 can be secured in place.

If the shielded cable is not secured, unevenness or movement of the shielded

cable or careless pulling on it could result in damage to the QD75 or drive unit or

shielded cable or defective cable connections could cause mis-operation of the

unit.

(9) If the cable connected to the QD75 and the power line must be adjacently laid

(less than 100mm), use a shielded cable. Ground the shield of the cable securely

to the control panel on the QD75 side.

(A wiring example is given on the next

page.)