F140, F141, F142 – Toshiba H9 User Manual

Page 103: F138

Advertising
background image

H9 ASD Installation and Operation Manual

95

Output Terminal 9 (R2) Function

Program

Terminal

Output Terminals

This parameter is used to set the functionality of the R2 discrete output
terminal.

In addition, this output terminal must be specified as Normally Open or
Normally Closed.

This setting assigns the function of the programmable R2 terminal to any one of
the user-selectable functions listed in

Table 8 on pg. 241

.

Note:

The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.

See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.

Direct Access Number — F138

Parameter Type — Selection List

Factory Default — Always Off

Changeable During Run — No

Input Terminal 1 (F) Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F140

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 2 (R) Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the drive to any change in the R terminal
input by the programmed value (see waveforms at

F140

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F141

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 3 (ST) Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the drive to any change in the ST
terminal input by the programmed value (see waveforms at

F140

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F142

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

F138

F142

Advertising