FM Bias Adjustment

Program

Terminal

Analog Output Terminals

This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.

Set the function of

F005

to zero and then set this parameter to zero for proper

operation.

See

F005

for more information on this setting.

Direct Access Number — F683

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -10.0

Maximum — +100.0

Units — %

AM Output Gradient Characteristic

Program

Terminal

Analog Output Terminals

This parameter sets the output response polarity of the AM output terminal.

The AM output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.

See

F670

for more information on this setting.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F685

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

AM Bias Adjustment

Program

Terminal

Analog Output Terminals

This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.

Set the function set at

F670

to zero and then set this parameter to zero for

proper operation.

See

F670

for more information on this setting.

Direct Access Number — F686

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -10.0

Maximum — +100.0

Units — %

MON 1 Voltage/Current Output Switching

Program

Terminal

Analog Output Terminals

This parameter is used to set the output signal type of the MON1 output
terminal.

Settings

0 — -10V – +10V
1 — 0 – 10V
2 — 0 – 20 mA

Direct Access Number — F688

Parameter Type — Selection List

Factory Default — 0 – 10V

Changeable During Run — Yes

MON 1 Output Gradient Characteristic

Program

Terminal

Analog Output Terminals

This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.

See parameter

F672

for more information on this setting.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F689

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes