H9 ASD Installation and Operation Manual

Forward Run/Reverse Run Disable

Program

Frequency

Forward/Reverse Disable

This parameter Enables/Disables the Forward Run or Reverse Run mode.

If either direction is disabled, commands received for the disabled direction will
not be recognized.

If both directions are disabled, the received direction command will determine
the direction of the motor rotation.

Settings:

0 — Off
1 — Disable Reverse Run
2 — Disable Forward Run

Direct Access Number — F311

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

Random Mode

Program

Protection

Retry/Restart

This parameter adjusts the carrier frequency randomly. This feature is effective
in minimizing the negative effects of mechanical resonance.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F312

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Carrier Frequency Control Mode

Program

Special

Carrier Frequency

This parameter provides for the automatic decrease of the carrier frequency.

Select 1 to decrease the Carrier Frequency setting as a function of an
increased current requirement.

Selection 2 or 3 may also include an output voltage drop as a function of an
increased current requirement. The Carrier Frequency should be set below
4 kHz.

Settings:

0 — No Decrease and No Limit
1 — Valid Decrease and No Limit
2 — No Decrease and Limit Small Pulse
4 — Valid Decrease and Limit Small Pulse

Direct Access Number — F316

Parameter Type — Selection List

Factory Default — Valid Decrease and
No Limit

Changeable During Run — Yes

Synchronized Deceleration Time

Program

Protection

Undervoltage/Ridethrough

In the event that the Ridethrough function activates in a multiple-motor
application it will be necessary to manage the stopping motors synchronously
as not to damage the product being processed (e.g., wire spools, bobbin winder
for textile machines, etc.).

This parameter is used to minimize the product breakage during a momentary
power outage. This function stops multiple machines simultaneously or makes
them reach their respective command frequencies simultaneously by regulating
their deceleration times.

See parameter

F302

for more information on this setting.

Direct Access Number — F317

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000.0

Units — Seconds