H9 ASD Installation and Operation Manual

V/f Five-Point Setting Voltage 1

Program

Special

V/f Five-Point Setting

The V/f Five-Point Setting Voltage 1 establishes the output voltage level that
is to be associated with the frequency setting of

F190

(V/f Five-Point Setting

Frequency 1).

The

F701

parameter setting will determine if the on-screen selection for this

parameter appears in the form of a Voltage (V) or as a Percentage (%) of the
ASD rating.

If using Voltage as a unit of measure and with no voltage correction (

F307

Disabled), the limit of the on-screen display value for this parameter is 200
volts for the 230-volt ASD and 400 volts for the 460-volt ASD.

The actual output voltage is scaled to the maximum EOI display values (e.g., a
100-volt EOI display corresponds to a 115-volt actual output for the 230-volt
ASD — ½ of the full display range).

If using % as a unit of measure and with no voltage correction (

F307

Disabled),

the ASD output voltage will be the percentage setting times 230 for the 230-
volt unit (or % times 460 volts for the 460-volt unit).

See

F190

for additional information on this setting.

Direct Access Number — F191

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (

F701

)

V/f Five-Point Setting Frequency 2

Program

Special

V/f Five-Point Setting

The Custom V/f Five-Point Setting Frequency 2 sets the frequency to be
associated with the voltage setting of parameter

F193

(V/f Five-Point Setting

Voltage 2).

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F192

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — No

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F191

F192