RR Input Point 2 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control
mode or the Torque Control mode.

This parameter sets the RR input level that is associated with RR Input Point 2
Frequency

when operating in the Speed control mode or is associated with the

RR Input Point 1 Rate when operating in the Torque Control mode.

This value is entered as 0% to 100% of the RR input signal range.

See RR Input Point 1 Setting for more information on this setting when used
for Speed control.

See RR Input Point 1 Rate for more information on this setting when used for
Torque Control.

Direct Access Number — F212

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

RR Input Point 2 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control
mode.

This parameter sets RR Input Point 2 Frequency and is the frequency that is
associated with the setting of RR Input Point 2 Setting when operating in the
Speed Control mode.

See RR Input Point 1 Setting for more information on this setting.

Direct Access Number — F213

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F212

F213