F205 – Toshiba H9 User Manual

Page 115

Advertising
background image

H9 ASD Installation and Operation Manual

107

V/I Input Point 1 Rate

Program

Torque

Setpoints

This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control
mode.

V/I Input Torque Control Setup

Perform the following setup to allow the system to receive Torque Control
input at the V/I input terminal:

• Set SW301 of the Terminal Board to Voltage or Current (see

Figure 9 on

pg. 24

).

• Program

⇒ Frequency ⇒ V/I Settings ⇒ V/I Voltage or Current input

signal.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode 1

V/I.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Selection

Terminal Block.

Torque Control

Perform the following setup to allow the system to perform Torque Control
from the V/I input terminal:

• Set V/I Input Point 1 Rate (

F205

).

• Set V/I Input Point 1 Setting (

F201

) — the input analog signal level that

corresponds to the torque setting at V/I Input Point 1 Rate.

• Set V/I Input Point 2 Rate (

F206

).

• Set V/I Input Point 2 Setting (

F203

) — the input analog signal level that

corresponds to the torque setting at V/I Input Point 2 Rate.

• Provide a Run command (F and/or R).

Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.

Once set, as the V/I input voltage changes or the V/I current changes, the
output torque of the ASD will vary in accordance with the above settings.

This parameter sets V/I Input Point 1 Rate and is the output torque value that
is associated with the setting of V/I Input Point 1 Setting when operating in
the Torque Control mode.

This value is entered as 0% to 250% of the rated torque.

Note:

When using the isolated V/I input terminal the IICC terminal
must be used as the return (negative) connection.

Direct Access Number — F205

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.00

Units — %

Torque Settings

F205

F205