Stall prevention level, F601, Motor – Toshiba H9 User Manual

Page 190: Overload protection level 1 on pg. 182, F600, F602, F574, F575

Advertising
background image

182

H9 ASD Installation and Operation Manual

Preset Speed 14 Operation Mode

Program

Pattern Run

Operation Mode

Same as Preset Speed 1 Operation Mode (see

F561

).

Direct Access Number — F574

Parameter Type — Selection List

Factory Default — Forward Run

Changeable During Run — No

Preset Speed 15 Operation Mode

Program

Pattern Run

Operation Mode

Same as Preset Speed 1 Operation Mode (see

F561

).

Direct Access Number — F575

Parameter Type — Selection List

Factory Default — Forward Run

Changeable During Run — No

Motor Overload Protection Level 1

Program

Fundamental

Motor Set #1

This parameter specifies the motor overload current level for motor set #1. This
value is entered as either a percentage of the full load rating of the ASD or as a
percentage of the FLA of the motor.

The unit of measurement for this parameter may be set to A/V (Amps) or it may
be set as a percentage of the ASD rating. The name-plated FLA of the motor
may be entered directly when Amps is selected as the unit of measurement (see

F701

to change the display unit).

Motor Overload Protection Level 1 settings will be displayed in Amps if the
EOI display units are set to A/V rather than %.

Direct Access Number — F600

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 10

Maximum — 100.0

Units — %

Stall Prevention Level

Program

Protection

Stall

This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The overcurrent level is entered as a
percentage of the maximum rating of the drive.

Note:

The Motor Overload Protection parameter must enabled at

F017

to use this feature.

Direct Access Number — F601

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 10

Maximum — 165

Units — %

Retain Trip Record at Power Down

Program

Protection

Trip Settings

This parameter Enables/Disables the Trip Record Retention setting. When
enabled, this feature logs the trip event and retains the trip information when the
system powers down. The trip information may be viewed from the (Program

⇒ Utilities ⇒) Trip History screen or the Monitor screen.
When disabled, the trip information will be cleared when the system powers
down.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F602

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

F574