F802, F803, F804 – Toshiba H9 User Manual

Page 213

Advertising
background image

H9 ASD Installation and Operation Manual

205

ASD Number

Program

Communications

Communication Settings

This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Direct Access Number — F802

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 247

Communications Time Out Time (RS485 2- and 4-wire)

Program

Communications

Communication Settings

This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Direct Access Number — F803

Parameter Type — Numerical

Factory Default — 0 (Off)

Changeable During Run — Yes

Minimum — 0 (Off)

Maximum — 100

Units — Seconds

Communications Time-Out Action (RS485 2- and 4-wire)

Program

Communications

Communication Settings

This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out
Action
).

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the drive.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

(settings are for 2-wire/4-wire)

0 — No Action/No Action
1 — Alarm/No Action
2 — Trip/No Action
3 — No Action/Alarm
4 — Alarm/Alarm
5 — Trip/Alarm
6 — No Action/Trip
7 — Alarm/Trip
8 — Trip/Trip

Direct Access Number — F804

Parameter Type — Selection List

Factory Default — Trip/Trip

Changeable During Run — Yes

F802

F804