170

H9 ASD Installation and Operation Manual

Deceleration Time 4

Program

Special

Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The
Accel/Decel pattern may be set using

F502

. The minimum Accel/Decel time

may be set using

F508

.

Note:

A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel
, Stall, and Ridethrough settings may lengthen the
deceleration times.

Direct Access Number — F515

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration/Deceleration Pattern 4

Program

Special

Accel/Decel #1 – #4 Settings

This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #4 Accel/Decel
parameter.

Settings:

0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2

Direct Access Number — F516

Parameter Type — Selection List

Factory Default — Linear

Changeable During Run — Yes

Acceleration/Deceleration Switching Frequency 3

Program

Special

Accel/Decel Special

This parameter sets the frequency at which the acceleration control is switched
from the Accel #3 profile to the Accel #4 profile during a multiple-acceleration
profile configuration.

Direct Access Number — F517

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Pattern Operation Selection

Program

Pattern Run

Pattern Run

Pattern Run operation is enabled by selecting Seconds or Minutes as a unit of
measure for the Operation Time setting for the selected Preset Speeds.

See Parameter

F523

for more information on Selections and Group Speeds

setup.

Settings:

0 — Disabled
1 — Enabled (units in seconds)
2 — Enabled (units in minutes)

Direct Access Number — F520

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Pattern Operation Mode

Program

Pattern Run

Pattern Run

This parameter sets the start condition of subsequent Pattern Runs after the
initial Pattern Run has been terminated or has completed its programming.

Settings:

0 — Reset After Stop
1 — Continue After Stop

Direct Access Number — F521

Parameter Type — Selection List

Factory Default — Reset After Stop

Changeable During Run — No

F515