H9 ASD Installation and Operation Manual

105

V/I Input Point 1 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control
mode or the Torque Control mode.

This parameter sets the V/I input level that is associated with the V/I Input
Point 1 Frequency
setting when operating in the Speed control mode or is
associated with the V/I Input Point 1 Rate setting when operating in the
Torque Control mode.

Note: See note on

pg. 44

for more information on the V/I terminal.

V/I Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input
at the V/I input terminal:

• Set SW301 of the Terminal Board to Voltage or Current (see

Figure 9 on

pg. 24

).

• Program

⇒ Frequency ⇒ V/I Settings ⇒ V/I Voltage or Current input

signal.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode

1

V/I.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Selection

Terminal Block.

Speed Control

Perform the following setup to allow the system to perform Speed control from
the V/I input terminal:

• Set V/I Input Point 1 Frequency (

F202

).

• Set V/I Input Point 1 Setting (

F201

) — the input analog signal level that

corresponds to the frequency setting at V/I Input Point 1 Frequency.

• Set V/I Input Point 2 Frequency (

F204

).

• Set V/I Input Point 2 Setting (

F203

) — the input analog signal level that

corresponds to the frequency setting at V/I Input Point 2 Frequency.

• Provide a Run command (F and/or R).

Once set, as the V/I input voltage or current changes, the output frequency of
the ASD will vary in accordance with the above settings.

This parameter value is entered as 0% to 100% of the V/I input signal range.

The V/I input is commonly used for a 4 – 20 mA current loop signal where

4 mA equals 20% of a 20 mA signal, set this parameter to 20% for 4 – 20 mA
current loop signal applications.

Note:

When using the isolated V/I input terminal the IICC terminal
must be used as the return (negative) connection.

Direct Access Number — F201

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

Frequency Settings