F371, F372, F373 – Toshiba H9 User Manual

Page 158: F375, F376

Advertising
background image

150

H9 ASD Installation and Operation Manual

PID Output Lower Limit

Program

Feedback

Feedback Settings

Selecting Speed PID at parameter

F359

allows for this parameter setting to

function as the Lower Limit while operating in the PID Control mode.

Direct Access Number — F371

Parameter Type — Numerical

Factory Default — 4.00

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

Process Increasing Rate

Program

Feedback

Feedback Settings

This parameter is used to limit the rate that the output of the ASD may increase
for a given difference in the speed reference and the PID feedback value.

Direct Access Number — F372

Parameter Type — Numerical

Factory Default — 10.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 600.0

Units — Seconds

Process Decreasing Rate

Program

Feedback

Feedback Settings

This parameter is used to limit the rate that the output of the ASD may decrease
for a given difference in the speed reference and the PID feedback value.

Direct Access Number — F373

Parameter Type — Numerical

Factory Default — 10.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 600.0

Units — Seconds

Number of PG Input Pulses

Program

Feedback

PG Settings

This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).

Direct Access Number — F375

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 12

Maximum — 9999

Number of PG Input Phases

Program

Feedback

PG Settings

This parameter determines the type of information that is supplied by the phase
encoder.

Settings:

1 — Single Phase
2 — Two Phase

Direct Access Number — F376

Parameter Type — Selection List

Factory Default — (ASD-dependent)

Changeable During Run — Yes

F371

F376