H9 ASD Installation and Operation Manual

235

Traverse Selection

Program

Special

Traverse

This parameter setting is used in the setup of the Traverse control mode of
operation and is used in conjunction with the discrete terminal activation of the
Traverse Permission Signal.

This parameter is used to enable the Traverse function. The Traverse function
is activated via the discrete input terminal (see

Table 5 on pg. 236

).

See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F980

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Traverse Acceleration Time

Program

Special

Traverse

This parameter setting is used in the setup of the Traverse control mode of
operation. This setting establishes the acceleration rate used during the
Traverse function.

See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.

Direct Access Number — F981

Parameter Type — Numerical

Factory Default — 25.0

Changeable During Run — No

Minimum — 0.1

Maximum — 120.0

Units — Seconds

Traverse Deceleration Time

Program

Special

Traverse

This parameter setting is used in the setup of the Traverse control mode of
operation. This setting establishes the deceleration rate used during the
Traverse function.

See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.

Direct Access Number — F982

Parameter Type — Numerical

Factory Default — 25.0

Changeable During Run — No

Minimum — 0.1

Maximum — 120.0

Units — Seconds

Traverse Step

Program

Special

Traverse

This parameter setting is used in the setup of the Traverse control mode of
operation. This setting is used as a multiplier to establish the amount that the
frequency is increased or decreased while using the Traverse function.

See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.

Direct Access Number — F983

Parameter Type — Numerical

Factory Default — 10.0

Changeable During Run — No

Minimum — 0.0

Maximum — 25.0

Units — %

Traverse Jump Step

Program

Special

Traverse

This parameter setting is used in the setup of the Traverse control mode of
operation. This setting is used as a multiplier to establish the amount that the
frequency is increased or decreased while using the Traverse function when a
short burst of rapid speed change is required.

See the Traverse Control Instruction Manual (P/N 58693) for more
information on this feature.

Direct Access Number — F984

Parameter Type — Numerical

Factory Default — 10.0

Changeable During Run — No

Minimum — 0.0

Maximum — 50.0

Units — %