H9 ASD Installation and Operation Manual

193

Adding Input Selection

Program

Feedback

Override Control

This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.

Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.

Settings:

0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 (2-wire)
6 — RS485 (4-wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (terminal board)
11 — Pulse Input (option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (option)

Direct Access Number — F660

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Multiplying Input Selection

Program

Feedback

Override Control

This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.

Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed Output Frequency.

If operating using the LED Keypad Option and Setting is selected, the value
entered at

F729

is used as the multiplier.

Settings:

0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —

F729

(setting)

5 — RX2 Option (AI1)

Direct Access Number — F661

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No