F007, F008 – Toshiba H9 User Manual

Page 87

Advertising
background image

H9 ASD Installation and Operation Manual

79

Type Reset

Program

Utilities

This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-reset configurations.

Settings:

0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — Save User Settings
8 — Restore User Settings
9 — Clear Cumulative Fan Timer
10 — Accel/Decel Time Setting 0.01 – 600.0 Seconds
11 — Accel/Decel Time Setting 0.1 – 6000.0 Seconds
12 — Update EOI Firmware
13 — Set EOI Memory to Default
14 — Save User Settings to EOI
15 — Restore User Settings from EOI

Direct Access Number — F007

Parameter Type — Selection List

Factory Default — None

Changeable During Run — No

Forward/Reverse Run Selection

Program

Fundamental

Standard Mode Selection

While operating using the keypad (

F003

is set to EOI Keypad) this parameter

sets the direction of motor rotation. This setting may be changed during
operation. This setting will not override parameter

F311

(Forward/Reverse

Disable).

If either direction is disabled via parameter

F311

, the disabled direction will not

be recognized if commanded by the keypad. If both directions are disabled via
parameter

F311

, the direction command from the keypad will determine the

direction of the motor rotation.

Settings:

0 — Forward
1 — Reverse
2 — Forward (EOI-switchable F/R)
3 — Reverse (EOI-switchable F/R)

Direct Access Number — F008

Parameter Type — Selection List

Factory Default — Forward

Changeable During Run — Yes

Reset

F007

F008