H9 ASD Installation and Operation Manual

V/I Input Point 1 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control
mode.

This parameter sets V/I Input Point 1 Frequency and is the frequency that is
associated with the setting of V/I Input Point 1 Setting when operating in the
Speed Control mode.

See V/I Input Point 1 Setting for more information on this setting.

Direct Access Number — F202

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

V/I Input Point 2 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control
mode or the Torque Control mode.

This parameter sets the V/I input level that is associated with V/I Input Point 2
Frequency

when operating in the Speed control mode or is associated with the

V/I Input Point 1 Rate when operating in the Torque Control mode.

This value is entered as 0% to 100% of the V/I input signal range.

See V/I Input Point 1 Setting for more information on this setting when used
for Speed control.

See V/I Input Point 1 Rate for more information on this setting when used for
Torque Control.

Direct Access Number — F203

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

V/I Input Point 2 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control
mode.

This parameter sets V/I Input Point 2 Frequency and is the frequency that is
associated with the setting of V/I Input Point 2 Setting when operating in the
Speed Control mode.

See V/I Input Point 1 Setting for more information on this setting.

Direct Access Number — F204

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F202

F204