H9 ASD Installation and Operation Manual

FLC

FLC is the common leg of a single-pole double-throw form C relay. The FL relay is the Fault

Relay by default, but may be programmed to any one of the conditions listed in

Table 8 on pg. 241

. For

further information on this terminal see

F132

and

Figure 8

.

FLB

— The normally-closed leg of the FL relay.

FLA

— The normally-open leg of the FL relay.

Note:

The FLA, FLB, and FLC contacts are rated at 2A/120 VAC and 2A/30 VDC.

Figure 8. FLA, FLB, and FLC switching contacts shown in the de-energized state.

Figure 9. Terminal Board.

Sink Source

See the section titled

Terminal Descriptions on pg. 22

for terminal descriptions.

See the section titled

Cable/Terminal/Torque Specifications on pg. 265

for information on the proper

cable/terminal sizes and torque specifications when making Terminal Board connections.

FLC

FLB

FLA

Note:

The relay is shown in the Faulted or de-energized condition.

During normal system operation the relay connection is FLC-
to-FLA.

J101

TB1

TB2

TB3

J100

SW200

TB4

SW301

RE

S

CC

F

R

S1

S2

S3

S4

CC

ST

FP

+S

U

Ensure that the ground screw is securely in place to
prevent arcing, intermittent operation, or system
failure.

1 to 2 = Sink

2 to 3 = Source

1 to 2 = System Supplied

2 to 3 = Ext. Supplied

(24V)

V/I Switch

See

Figure 20 on pg. 26

for more information on the Terminal Board connections.

Half/Full Duplex Switch

CAUTION

S4

RS485 4-Wire Communication