H9 ASD Installation and Operation Manual

199

Display Units for Voltage and Current

Program

Utilities

Display Parameters

This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.

Settings:

0 — %
1 — A/V

Direct Access Number — F701

Parameter Type — Selection List

Factory Default — %

Changeable During Run — Yes

Display Unit Multiplication Factor

Program

Utilities

Display Parameters

This parameter provides a multiplier for the displayed speed value shown on the
front panel display of the ASD.

This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).

Example: An output frequency of 100 Hz would be displayed as 50 Hz if

using a multiplier of 0.5 for this parameter.

Note:

PID frequency-limiting parameters are not affected by this
setting (i.e.,

F364

,

F365

,

F367

, and

F368

).

Direct Access Number — F702

Parameter Type — Numerical

Factory Default — 0.00 (OFF)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 200.00

Display Unit Selection

Program

Utilities

Display Parameters

This parameter is used in conjunction with

F702

to set the method in which the

frequency is displayed on the front panel.

The multiplier setting of

F702

will be applied to the display of all frequencies if

All Frequencies are selected at this parameter.

The multiplier setting of

F702

will be applied to parameters

F364

,

F365

,

F367

,

and

F368

ONLY if PID Process Data is selected at this parameter.

Settings:

0 — All Frequencies
1 — PID Process Data

Direct Access Number — F703

Parameter Type — Selection List

Factory Default — All Frequencies

Changeable During Run — Yes

Display Gradient Characteristic

Program

Utilities

Display Parameters

The ASD-displayed response to output speed changes will be displayed as
directly proportional or inversely proportional as a function of this parameter
setting.

Selecting Negative Gradient displays an increased output speed as going more
negative.

Selecting Positive Gradient displays an increased output speed as going more
positive.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F705

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

F701

F705