F193, F194, F195 – Toshiba H9 User Manual

Page 111: F196, F197

Advertising
background image

H9 ASD Installation and Operation Manual

103

V/f Five-Point Setting Voltage 2

Program

Special

V/f Five-Point Setting

The V/f Five-Point Setting Voltage 2 establishes the output voltage level that
is to be associated with the frequency setting of

F192

(V/f Five-Point Setting

Frequency 2).

The

F701

parameter setting will determine if the selection for this parameter

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

The default setting is %.

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F193

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (

F701

)

V/f Five-Point Setting Frequency 3

Program

Special

V/f Five-Point Setting

The Custom V/f Five-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter

F195

(V/f Five-Point Setting

Voltage 3).

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F194

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — No

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

V/f Five-Point Setting Voltage 3

Program

Special

V/f Five-Point Setting

The V/f Five-Point Setting Voltage 3 establishes the output voltage level that
is to be associated with the frequency setting of

F194

(V/f Five-Point Setting

Frequency 3).

The

F701

parameter setting will determine if the selection for this parameter

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

The default setting is %.

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F195

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (

F701

)

V/f Five-Point Setting Frequency 4

Program

Special

V/f Five-Point Setting

The Custom V/f Five-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter

F197

(V/f Five-Point Setting

Voltage 4).

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F196

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — No

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

V/f Five-Point Setting Voltage 4

Program

Special

V/f Five-Point Setting

The V/f Five-Point Setting Voltage 4 establishes the output voltage level that
is to be associated with the frequency setting of

F196

(V/f Five-Point Setting

Frequency 4).

The

F701

parameter setting will determine if the selection for this parameter

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

The default setting is %.

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F197

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (

F701

)

F193

F197