H9 ASD Installation and Operation Manual

Selection of OUT Terminal

Program

Terminal

Analog Output Terminals

This parameter is used to enable the OUT1 and OUT2 output terminals, or the
FP output terminal by selecting Logic Output or Pulse Train Output,
respectively.

Note:

The Logic output and the Pulse Train output may not be used
simultaneously.

If Logic Output is selected the OUT1 and OUT2 (O1A/O1B and O2A/O2B)
output contacts of the Terminal Board are enabled to function as described in
parameter

F130

.

The OUT1 and OUT2 terminals may be used simultaneously and they may be
assigned different functions.

If Pulse Train Output is selected the FP output terminal of the Terminal Board
is enabled to function as configured in

F676

and

F677

.

Settings:

0 — Logic Output
1 — Pulse Train Output

Direct Access Number — F669

Parameter Type — Selection List

Factory Default — Pulse Train Output

Changeable During Run — No

AM Output Terminal Function

Program

Terminal

Analog Output Terminals

This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in

Table 6 on pg. 239

.

Note: To read current at this terminal connect a 100 – 500

Ω

resistor from

the AM (+) terminal through the series Ammeter to the CC (-)
terminal.

The FM analog output has a maximum resolution of 1/1024 and a
maximum load rating of 500 ohms.

AM Terminal Setup Parameters

F670

— Set AM Function

F671

— Calibrate AM Terminal

F685

— Output Response Polarity Selection

F686

— Set Zero Level

Direct Access Number — F670

Parameter Type — Selection List

Factory Default — Output Current

Changeable During Run — Yes

AM Output Terminal Adjustment

Program

Terminal

Analog Output Terminals

This parameter is used to calibrate the AM analog output.

To calibrate the AM analog output, connect an ammeter as described at
parameter

F670

.

With the drive running at a known value (e.g., output frequency), adjust this
parameter until the assigned function (parameter

F670

) produces the desired

DC level output at the AM output terminal.

See

F670

for more information on this setting.

Direct Access Number — F671

Parameter Type — Numerical

Factory Default — 512

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

AM

F669