F633, F634, F635 – Toshiba H9 User Manual

Page 199: F637

Advertising
background image

H9 ASD Installation and Operation Manual

191

V/I Analog Input Broken Wire Detection Level

Program

Terminal

Input Special Functions

This parameter is enabled by providing a non-zero value here. This function
monitors the V/I input signal and if the V/I input signal falls below the level
specified here and remains there for a period of 0.3 seconds or more a trip will
be incurred (E-18).

This value is entered as 0% to 100% of the V/I input signal range.

Direct Access Number — F633

Parameter Type — Numerical

Factory Default — 0 (Disabled)

Changeable During Run — No

Minimum — 1

Maximum — 100

Units — %

Annual Average Ambient Temperature

Program

Special

Special Parameters

This parameter is used in conjunction with a discrete output terminal setting to
notify the operator of the remaining useful life of critical components of the
ASD system.

With a discrete output terminal set to Part Replacement Alarm (see

Table 8 on

pg. 241

) and the calculation derived from the parameter setting, maintenance

scheduling may be enhanced.

Settings:

1 — Under 10° C (50° F)
2 — Under 20° C (68° F)
3 — Under 30° C (86° F)
4 — Under 40° C (104° F)
5 — Under 50° C (122° F)
6 — Under 60° C (140° F)

Direct Access Number — F634

Parameter Type — Selection List

Factory Default — Under 30°

Changeable During Run — No

Rush Relay Current Activation Time

Program

Special

Special Parameters

Rush Relay Current

Activation Time

At system startup, this parameter sets a time-delay for the start of the Rush
Relay
activation in an attempt to allow the DC bus voltage to reach the normal
operating level before outputting a signal to the motor.

Direct Access Number — F635

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 2.5

Units — Seconds

PTC1 Thermal Selection

Program

Special

Special Parameters

PTC1 Thermal Selection

This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 1. A thermistor is connected from TH1+ to
TH1- of TB3 on the Expansion IO Card Option 1.

Should the thermistor resistance reading fall below 50

Ω because of an over-

temperature condition or exceed 3000

Ω because of an open circuit an External

Thermal Fault (OH2) will be incurred.

Note:

While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8k

Ω from an

over-temperature condition. An Auto-restart will not be initiated
subsequent to an External Thermal Trip (OH2). A manual
restart will be required in the event of an OH2 trip.

Settings:

0 — Disabled
1 — Detect Disconnect

Direct Access Number — F637

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

F633

F637