F959, F961, F962 – Toshiba H9 User Manual

Page 236

Advertising
background image

228

H9 ASD Installation and Operation Manual

Analog Input Function Target 11

Program

My Function

My Function Analog

This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Analog Input Function Target
11
terminal.

The function selected at

F961

may be adjusted using the input analog control

signal selected here.

Settings:

0 — Disabled (None)
1 — V/I
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I

Direct Access Number — F959

Parameter Type — Selection List

Factory Default — 0 (Disabled)

Changeable During Run — Yes

Analog Function Assigned Object 11

Program

My Function

My Function Analog

This parameter plays a role in the setup of the My Function feature by
selecting the functionality to which the adjustment of

F959

is applied.

Settings:

0 — Disabled (None)
1 — Acceleration Rate
2 — Upper Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over Current Stall (

F601

)

7 — Thermal Protection
8 — Speed Loop P Gain (

F460

)

9 — Drooping Gain (

F320

)

10 — PID P Gain (

F362

)

See the My Function Instruction Manual (P/N 58692) for a complete
description of the setup requirements and operational information of the Analog
Function Assigned Object
parameter.

Direct Access Number — F961

Parameter Type — Selection List

Factory Default — 0 (Disabled)

Changeable During Run — Yes

Analog Input Function Target 21

Program

My Function

My Function Analog

This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Analog Input Function Target
21
terminal.

The function selected at

F964

may be adjusted using the input analog control

signal selected here.

Settings:

0 — Disabled (None)
1 — V/I
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I

Direct Access Number — F962

Parameter Type — Selection List

Factory Default — 0 (Disabled)

Changeable During Run — Yes

F959

F962

Advertising