F223, F224, F225 – Toshiba H9 User Manual

Page 125

Advertising
background image

H9 ASD Installation and Operation Manual

117

RX2 (AI1) Input Point 1 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.

This parameter sets RX2 (AI1) Input Point 1 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 1 Setting when
operating in the Speed Control mode.

See RX2 (AI1) Input Point 1 Setting for more information on this setting.

Direct Access Number — F223

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

RX2 (AI1) Input Point 2 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.

This parameter sets the RX2 (AI1) input level that is associated with RX2
(AI1) Input Point 2 Frequency

when operating in the Speed control mode or

is associated with the RX2 (AI1) Input Point 2 Rate when operating in the
Torque Control mode.

This value is entered as -100% to +100% of the RX2 (AI1) input signal range.

See RX2 (AI1) Input Point 1 Setting for more information on this setting
when used for Speed control.

See RX2 (AI1) Input Point 1 Rate for more information on this setting when
used for Torque Control.

Direct Access Number — F224

Parameter Type — Numerical

Factory Default — +100

Changeable During Run — Yes

Minimum — -100

Maximum — +100

Units — %

RX2 (AI1) Input Point 2 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.

This parameter sets RX2 (AI1) Input Point 2 Frequency and is the frequency
that is associated with the setting of RX2 (AI1) Input Point 2 Setting when
operating in the Speed Control mode.

See RX2 (AI1) Input Point 1 Setting for more information on this setting.

Direct Access Number — F225

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F223

F225