BIN Input Point 1 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the speed of the BIN input terminals when the
BIN terminals are used as the control input.

This parameter sets BIN Input Point 1 Frequency and is the frequency that is
associated with the setting of BIN Input Point 1 Setting.

See BIN Input Point 1 Setting for further information on this setting.

Direct Access Number — F229

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0

Maximum — Max. Freq. (

F011

)

Units — Hz

BIN Input Point 2 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the speed of the BIN input terminals when the
BIN terminals are used as the control input.

This parameter sets the BIN input signal that is associated with BIN Input
Point 2 Frequency
.

This value is entered as 0% to +100% of the BIN input signal range.

See BIN Input Point 1 Setting for further information on this setting.

Direct Access Number — F230

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

BIN Input Point 2 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the speed of the BIN input terminals when the
BIN terminal are used as the control input.

This parameter sets BIN Input Point 2 Frequency and is the frequency that is
associated with the setting of BIN Input Point 2 Setting.

See BIN Input Point 1 Setting for further information on this setting.

Direct Access Number — F231

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Maximum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F229