H9 ASD Installation and Operation Manual

125

DC Injection Braking Time

Program

Protection

DC Braking

This parameter setting is used to set the on-time duration of the DC Injection
Braking
.

Direct Access Number — F252

Parameter Type — Numerical

Factory Default — 1.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 20.0

Units — Seconds

Forward/Reverse DC Injection Braking Priority

Program

Protection

DC Braking

This parameter setting determines if DC Injection braking is to be used during
a change in the direction of the motor.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F253

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Motor Shaft Fixing Control

Program

Protection

DC Braking

This parameter Enables/Disables a continuous DC injection at half of the
amperage setting of

F251

into a stopped motor. This feature is useful in

preheating the motor or to keep the rotor from spinning freely.

Motor Shaft Stationary Control starts after the DC injection brake stops the
motor and continues until STCC is opened, power is turned off, an
Emergency Off command is received, or this parameter is changed.

Enabling this feature will also require a non-zero entry at

F250

.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F254

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

0 Hz Command Output

Program

Special

Special Parameters

This parameter is used to set the go-to-zero method to be used by the ASD in
the event that the ASD is commanded to go to zero Hz.

Settings:

0 — Standard (DC Injection Braking)
1 — 0 Hz Command

Direct Access Number — F255

Parameter Type — Selection List

Factory Default — Standard (DC
Injection Braking)

Changeable During Run — No

Time Limit For Lower-Limit Frequency Operation

Program

Fundamental

Frequency Settings

This parameter sets the time that the ASD is allowed to operate below the
Lower Limit setting before an alarm and subsequent fault is incurred.

Direct Access Number — F256

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 600.0

Units — Seconds

F252

F256