H9 ASD Installation and Operation Manual

RX2 (AI1) Input Point 1 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.

Note:

The Expansion IO Card Option 1 option board (P/N ETB003Z)
is required to use this terminal.

This parameter sets the RX2 (AI1) input level that is associated with RX2
(AI1) Input Point 1 Frequency
when operating in the Speed Control mode or
is associated with the RX2 (AI1) Input Point 1 Rate when operating in the
Torque Control mode.

RX2 (AI1) Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input
at the RX2 (AI1) input terminal:

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode

1

RX2.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Selection

Terminal Block.

Speed Control

Perform the following setup to allow the system to perform Speed control from
the RX2 (AI1) input terminal:

• Set RX2 (AI1) Input Point 1 Frequency (

F223

).

• Set RX2 (AI1) Input Point 1 Setting (

F222

) — the input analog signal

level that corresponds to the speed setting at RX2 (AI1) Input Point 1
Frequency
.

• Set RX2 (AI1) Input Point 2 Frequency (

F225

).

• Set RX2 (AI1) Input Point 2 Setting (

F224

) — the input analog signal

level that corresponds to the speed setting at RX Input Point 2 Frequency.

• Provide a Run command (F and/or R).

Once set, as the RX2 (AI1) input voltage changes, the ASD output speed and/or
torque will vary in accordance with the above settings.

This parameter value is entered as -100% to +100% of the RX2 (AI1) input
signal range.

See the Expansion IO Card Option 1 instruction manual (P/N 58685) for
more information on the function of this terminal. And see parameter

F476

and

F477

for information on fine-tuning this terminal response.

Direct Access Number — F222

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — -100

Maximum — +100

Units — %

Frequency Settings

F222

F222