F349, F347, F348 – Toshiba H9 User Manual

Page 152

Advertising
background image

144

H9 ASD Installation and Operation Manual

Creeping Time

Program

Torque

Torque Control

Once the Creep function of

F346

is activated, this parameter determines the

duration of activation of the Creep function.

Direct Access Number — F347

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.0

Maximum — 2.50

Units — Seconds

Braking Time Learning Function

Program

Torque

Torque Control

This parameter is used to establish approximate settings for parameters

F343

,

F345

,

F346

, and

F347

.

Note:

Setting this parameter should be done using a light load only.

Set this parameter to Brake Signal Learning. Provide a Run command. The
aforementioned parameters will receive approximate values. Application-
specific adjustments may be required when done.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F348

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Accel/Decel Suspend

Program

Fundamental

Accel/Decel #1 Settings

To maintain a constant speed setting while running, this parameter may be used
to suspend speed changes for a user-set length of time.

The Accel/Decel Suspend function is enabled by setting this parameter to
either Terminal Board Input or to

F350

F353

.

Selecting Terminal Board Input at this parameter requires that a discrete input
terminal be set to Dwell Signal (see

Table 5 on pg. 236

for a listing of available

settings). Upon activation of the Dwell Signal terminal the output frequency
remains at the at-activation speed for the duration of the activation. When
deactivated the programmed accel or decel ramp resumes.

Selecting

F350

F353

at this parameter requires that the acceleration and/or

the deceleration Suspend Frequency and Suspend Time settings be completed
at

F350

,

F351

,

F352

, and

F353

. Upon reaching the frequency setting of

F350

(Accel) or

F352

(Decel), the Accel/Decel ramp will cease and the output

frequency will hold at the threshold frequency setting for the time setting of

F351

for Acceleration or

F353

for deceleration.

Settings:

0 — Off
1 —

F350

F353

Settings

2 — Terminal Board Input

Direct Access Number — F349

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — Yes

F347