F681, F676 on pg. 196, F682 – Toshiba H9 User Manual

Page 204: F675, F676, F677

Advertising
background image

196

H9 ASD Installation and Operation Manual

MON2 Terminal Adjustment

Program

Terminal

Analog Output Terminals

This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter

F674

.

See parameter

F674

for more information on this setting.

Direct Access Number — F675

Parameter Type — Numerical

Factory Default — 512

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

FP Terminal Assignment

Program

Terminal

Analog Output Terminals

This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in

Table 6 on pg. 239

and is enabled at

parameter

F669

.

As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.

Note:

The duty cycle of the output pulse train remains at 65 ±5.0 µ S.

This parameter is used in conjunction with parameter

F669

and

F677

.

Direct Access Number — F676

Parameter Type — Selection List

Factory Default — Output Frequency

Changeable During Run — Yes

Pulse Output Frequency

Program

Terminal

Analog Output Terminals

This parameter scales the FP output terminal by setting the pulses-per-second
output signal of the FP terminal.

See

F676

for more information on this parameter.

Direct Access Number — F677

Parameter Type — Numerical

Factory Default — 3.84

Changeable During Run — Yes

Minimum — 1.00

Maximum — 43.20

Units — Pulses/Second

FM Voltage/Current Output Switching

Program

Terminal

Analog Output Terminals

This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).

The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.

See

F005

for more information on this setting.

Settings:

0 — 0 – 10V
1 — 0 – 20 mA

Direct Access Number — F681

Parameter Type — Selection List

Factory Default — 0–10V

Changeable During Run — No

FM Output Gradient Characteristic

Program

Terminal

Analog Output Terminals

This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.

See

F005

for more information on this setting.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F682

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

FP

F675

F682