Terminal descriptions, Terminal descriptions on pg. 22 – Toshiba H9 User Manual

Page 30

Advertising
background image

22

H9 ASD Installation and Operation Manual

Terminal Descriptions

Note:

The programmable terminal assignments may be accessed and changed from their
default settings as mapped on

pg. 46

or via the Direct Access method: Program

Direct Access

applicable parameter number. See the section titled

Program Mode

Menu Navigation on pg. 46

for the applicable Direct Access parameter numbers.

For further information on terminal assignments and default setting changes, see the
sections titled

Default Setting Changes on pg. 74

and

Terminal on pg. 47

.

Note:

See the section titled

Cable/Terminal/Torque Specifications on pg. 265

for the H9

ASD conductor and terminal electrical specifications.

Note:

Programmable terminals will not retain their settings indefinitely in the event of a
power loss. Connect an external +24VDC supply to the SU+ terminal to retain the
programmable settings in the event of Control Power loss (see

Figure 20 on pg. 26

).

ST

— The default setting for this terminal is the Standby mode controller. As the default setting, this

terminal must be activated for normal system operation. The ST terminal is activated by connecting CC
to this terminal (Sink mode). When deactivated the Not Ready to Run icon is displayed on the LCD
screen as shown in

Figure 22. on pg. 31

.This input terminal may be programmed to any one of the

functions that are listed in

Table 5 on pg. 236

(see

F113

).

RES

— The default setting for this terminal is Reset. The RES terminal is activated by connecting CC

to this terminal (Sink mode). A momentary connection to CC resets the ASD and any fault indications
from the display. Reset is effective when faulted only. This input terminal may be programmed to any
one of the functions that are listed in

Table 5 on pg. 236

(see

F114

).

F

— The default setting for this terminal is the Forward Run Command. The F terminal is activated

by connecting CC to this terminal (Sink mode). This input terminal may be programmed to any one of
the functions that are listed in

Table 5 on pg. 236

(see

F111

).

R

— The default setting for this terminal is the Reverse Run Command. The R terminal is activated

by connecting CC to this terminal (Sink mode). This input terminal may be programmed to any one of
the functions that are listed in

Table 5 on pg. 236

(see

F112

).

S1

— The default setting for this terminal is the Preset Speed #1 Command. The S1 terminal is

activated by connecting CC to this terminal (Sink mode). This input terminal may be programmed to
any one of the functions that are listed in

Table 5 on pg. 236

(see

F115

).

S2

— The default setting for this terminal is the Preset Speed #2 Command. The S2 terminal is

activated by connecting CC to this terminal (Sink mode). This input terminal may be programmed to
any one of the functions that are listed in

Table 5 on pg. 236

(see

F116

).

S3

— The default setting for this terminal is the Preset Speed #3 Command. The S3 terminal is

activated by connecting CC to this terminal (Sink mode). This input terminal may be programmed to
any one of the functions that are listed in

Table 5 on pg. 236

(see

F117

).

S4

— The default setting for this terminal is the Preset Speed #4 Command. The S4 terminal is

activated by connecting CC to this terminal (Sink mode). This input terminal may be programmed to
any one of the functions that are listed in

Table 5 on pg. 236

(see

F118

).

RR

— The default function assigned to this terminal is the Frequency Mode 1 setting. The RR

terminal accepts a 0 – 10 VDC input signal that is used to carry out the function assigned to this
terminal. This input terminal may be programmed to control the speed or torque of the motor via an
amplitude setting or regulate by setting a limit. The gain and bias of this terminal may be adjusted for
application-specific suitability (see

F210

F215

). See

Figure 20 on pg. 26

for an electrical depiction of

the RR terminal. This terminal references CCA.

Advertising