H9 ASD Installation and Operation Manual

161

Second Speed Loop Stabilization Coefficient

Program

Feedback

PG Settings

During closed-loop operation, this parameter sets the response sensitivity of the
drive when monitoring the output speed for control.

The larger the value entered here, the quicker the response to changes in the
received feedback.

Direct Access Number — F464

Parameter Type — Numerical

Factory Default — 1

Changeable During Run — Yes

Minimum — 1

Maximum — 9999

Load Moment of Inertia 2

Program

Feedback

PG Settings

This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.

Direct Access Number — F465

Parameter Type — Numerical

Factory Default — 35

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Speed PID Switching Frequency

Program

Feedback

Feedback Settings

While running, this parameter establishes the threshold speed setting that is
used to determine if PID control may engage or remain engaged if active.

Direct Access Number — F466

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

V/I Input Bias

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine-tune the bias of the V/I input terminals.

Note:

See note on

pg. 43

for more information on the V/I terminal.

This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.

This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.

Direct Access Number — F470

Parameter Type — Numerical

Factory Default — 127

Changeable During Run — Yes

Minimum — 0

Maximum — 255

V/I Input Gain

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine tune the gain of the V/I input terminals.

Note:

See note on

pg. 43

for more information on the V/I terminal.

This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.

This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.

Direct Access Number — F471

Parameter Type — Numerical

Factory Default — 129

Changeable During Run — Yes

Minimum — 0

Maximum — 255

F464

F471