H9 ASD Installation and Operation Manual

149

PID Deviation Lower Limit

Program

Feedback

Feedback Settings

This parameter determines the maximum amount that the feedback may
decrease the output signal.

Direct Access Number — F365

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 60.00

Units — Hz

PID Feedback Differential (D) Gain

Program

Feedback

Feedback Settings

This parameter determines the degree that the Differential function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.

Direct Access Number — F366

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.55

Process Upper Limit

Program

Feedback

Feedback Settings

Selecting Process PID at parameter

F359

allows for this parameter setting to

function as the Upper Limit while operating in the PID Control mode.

Direct Access Number — F367

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — No

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

Process Lower Limit

Program

Feedback

Feedback Settings

Selecting Process PID at parameter

F359

allows for this parameter setting to

function as the Lower Limit while operating in the PID Control mode.

Direct Access Number — F368

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — No

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

PID Control Wait Time

Program

Feedback

Feedback Settings

This parameter is used to delay the start of PID control at start up. During the
wait time set here, the ASD will follow the frequency control input of the
process value and the feedback input will be ignored until this setting times out.
At which time the PID setup assumes control.

Direct Access Number — F369

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 2400

Units — Seconds

PID Output Upper Limit

Program

Feedback

Feedback Settings

Selecting Speed PID at parameter

F359

allows for this parameter setting to

function as the Upper Limit while operating in the PID Control mode.

Direct Access Number — F370

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — No

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

F365

F370