H9 ASD Installation and Operation Manual

195

MON1 Terminal Meter Selection

Program

Terminal

Analog Output Terminals

This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in

Table 6

on pg. 239

.

The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.

Note:

The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.

See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.

MON1 Terminal Setup Parameters

F672

— MON1 Output Function

F673

— MON1 Terminal Meter Adjustment

F688

— MON1 Voltage/Current Output Switching

F689

— MON1 Output Gradient Characteristic

F690

— MON1 Bias Adjustment Set Zero Level

Direct Access Number — F672

Parameter Type — Selection List

Factory Default — Output Voltage

Changeable During Run — Yes

MON1 Terminal Adjustment

Program

Terminal

Analog Output Terminals

This parameter is used to set the gain of the MON1 output terminal and is used
in conjunction with the settings of parameter

F672

.

See parameter

F672

for more information on this setting.

Direct Access Number — F673

Parameter Type — Numerical

Factory Default — 512

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

MON2 Terminal Meter Selection

Program

Terminal

Analog Output Terminals

This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in

Table 6

on pg. 239

.

The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.

Note:

The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.

See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.

MON2 Terminal Setup Parameters

F674

— MON2 Output Function

F675

— MON2 Terminal Meter Adjustment

F691

— MON2 Voltage/Current Output Switching

F692

— MON2 Output Gradient Characteristic

F693

— MON2 Bias Adjustment Set Zero Level

Direct Access Number — F674

Parameter Type — Selection List

Factory Default — Output Frequency

Changeable During Run — Yes

F672

F674